Home | About us | Equipment | Products | Marketing | Online order | Contact  
Chinese     English      
 
 Varistor
 Surge Arrester
 Fuse Cutout
 Porcelain Bushing
 Silicon Rubber
 Fibre Glass Tape
 epoxy rods

   
Porcelain Bushing Positions: Home - Porcelain Bushing - HV post insulator
 
hv post insulator2


 
Factory No.

22001

22002

22003

22004

22005

ANSI Class

TR-205

TR-208

TR-210

TR-214

TR-216

Fig. No

31

32

33

34

35

Creepage Distance mm

394

610

940

1092

1829

Cantilever Strength kN

8.9

8.9

8.9

8.9

6.7

Tensile Strength kN

38

44.5

53

62

71

Torsion Strength N. m

791

904

1130

1356

1695

Compression Strength kN

44.5

44.5

66.7

66.7

111

Low Frequency Flashover Voltage

Dry Flashover kv

85

110

145

170

235

Wet Flashover kv

55

75

100

125

180

Critical Impulse Flashover Voltage

Pos. kv

125

170

225

280

390

Neg. kv

200

250

290

340

475

WetLow Frequency Withstand voltage

Dry Withstand kv

50

70

95

120

175

Wet Withstand kv

45

60

80

100

145

Impulse Withstand Voltage kv

110

150

200

250

350

Net Weight Each Approx. kg

7

11

16

21

30

 
Back
 
 
 

TEL:86-731-5499326 FAX:86-731-5499356 Mobile Phone:137 861 88769
Email:sales@yyip.cn    tang731@163.com MSN:managertang731@hotmail.com
Website:http://www.yyip.cn
copyright © 2007 All Rights Reserved .Power by RICH